Electronic Trouble Shooting Of New Danfoss BD Compressors
This information was taken from Danfoss’ web page.
New Danfoss BD35F and BD50F compressors
are equipped with an electronic diagnostic circuit although most refrigeration
manufacturers do not provide the indicator light. A 10 mA light emitting diode
(LED) can be connected between the + fan terminal and D terminal of the electronic
module. If the electronic unit records an operational error the diode will flash
a number of times. The number of flashes depends on what kind of operational
error was recorded. Each flash will last ¼ second. After the actual number of
flashes, there will be a delay with no flashes, so that the sequence for each
error can be repeated every 4 seconds.
5 Flashes: Thermal cut-out of electronic unit
If the refrigeration system has been too
heavily loaded, or if the ambient temperature
is too high, the electronic
unit will run too hot.
4
Flashes:
Minimum motor speed error
If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed 1800 rpm.
3 Flashes: Motor start errors
The r
Motor is blocked or the differential pressure in the refrigeration system is
too high.
2 Flashes: Fan over-current cutout
The
Fan loads the electronic unit with more than one amp
1 Flash: Battery protection cutout
The voltage is outside the cutout
setting.