| Refrigerator performance is not affected by small variations in refrigeration charge. I add refrigerant until things get cold. True or False? |
|
This
is true on larger refrigeration systems that use expansion valves and
receiver tanks, as long as is not over serviced. But it is false when
applied to most small 12-volt units with capillary tubes. These units
are precharged by the manufacture with a specific volume of refrigerant
any loss during assembly or loss due to leakage means loss of
performance. In the field servicing is difficult even for an experienced
service technician. The volume of refrigerant for each of these small
units will vary from 1.8 to 4 ounces. Field
Service technicians rarely have the equipment to service a system by
volume and must adjust volume by monitoring
suction pressure. I have found that for best results adjustments
to refrigerant level can only be done with a warm box and the adjustment
must be done in the first 15 minutes of operation. After 15 minutes the
refrigerant starts to cool were by lowering the suction pressure.
|